Control system
CryoServer
Control system for cryogenic warehouses
Application
The CryoServer control system is designed to perform all essential functions required for the fully automatic and safe operation of a cryogenic storage system in cryogenic warehouses.
Structure
Features
- Integrated or externally adapted room air monitoring with user-guided function control
- Control and monitoring of the fill level and pressure of the supply tank
- Control of the safety shut-off valve - switch off in case of oxygen deficiency, emergency stop or excessive pressure
- Control of a phase separator, optionally with sub cooler function
- Control of manual or semi-automatic filling stations for Dewars or LN2 transport containers
- Monitoring of freezer containers with higher-level control of sequential and simultaneous filling via Modbus communication
- Visualisation of the supply system
- Directly viewable log, stored on SD card
- Password-protected setup
- Web-based visualisation for remote monitoring
Description
The CryoServer control system is equipped with a programmable controller that can be expanded with additional functions and control units, depending on the requirements of the cryogenic storage system. The system includes an UPS to bridge short-term power failures.
In addition to Ethernet and RS485 communication interfaces, the system features potential-free signalling contacts for forwarding alarms and faults to the building management system
Technical data
Dimensions | mm | H x W x D = 600 x 380(600) x 210 |
Weight | kg | 22 to 28 |
Operating Temperature | °C | -10 up to +40 |
Electr. supply | 230 VAC, 50 Hz, up to 1kW |
Pictures